Chapter 2 Add a PowerFlex 70 Drive to an RSLogix 5000 Project

Test the PowerFlex 70 Drive Tags

1.

Move the controller mode switch
to RUN.

2.

Double-click Controller Tags.

3.

On the Monitor Tags tab, expand
the PowerFlex 70 output tag and
change the ClearFault tag to 1 to
clear any initial faults.

4.

Change the ClearFault tag
back to 0.

5.

Expand the PowerFlex 70 input
tag and Verify that the
I.DriveStatus_Ready tag value is 1.

This tag indicates that the drive is
ready to start.