Step 11: Install the DC– Bus
Bar Assembly and Fuse

1. Secure the end of the DC– bus bar assembly to the insulated standoff on the

right side support bracket attached to the air flow plate using a M10x16 bolt
and flat and lock washer as shown below.

Verify that the bus bar closest to the front of the drive is in front of the DC–
terminal on the drive and that the connection holes align.

Important: Do not fully tighten this assembly. Final torque must be applied

after all bus bars have been installed.

Top View

Verify bus bar is in

front of DC-

terminal and holes

align

Note: only left side enclosure shown.

Support Bracket