Publication PFLEX-IN022A-EN-P

4

PowerFlex® 700S and 700H Frame 12 DC Bus Connector Kit

Step 1: Remove Power
from the Drive

1. Turn off and lock out input power. Wait five minutes.

2. Verify that there is no voltage at the drive’s input power terminals.

3. Check the DC bus voltage at the Power Terminal Block by measuring

between the +DC and –DC terminals, between the +DC terminal and the
chassis, and between the –DC terminal and the chassis. The voltage must be
zero for all three measurements.

ATTENTION: To avoid an electric shock hazard, verify that the
voltage on the bus capacitors has discharged completely before
servicing. Check the DC bus voltage at the Power Terminal
Block by measuring between the +DC and –DC terminals,
between the +DC terminal and the chassis, and between the –DC
terminal and the chassis. The voltage must be zero for all three
measurements.

Remove power before making or breaking cable connections.
When you remove or insert a cable connector with power
applied, an electrical arc may occur. An electrical arc can cause
personal injury or property damage by:
• sending an erroneous signal to your system’s field devices,

causing unintended machine motion

• causing an explosion in a hazardous environment

Electrical arcing causes excessive wear to contacts on both the
module and its mating connector. Worn contacts may create
electrical resistance.