PowerFlex® 700S and 700H Frame 12 DC Bus Connector Kit

29

Publication PFLEX-IN022A-EN-P

1. Verify that no power is applied to the drive.

2. Disconnect all motor leads from the drive.

3. Complete the forward and reverse biased diode tests on the rectifying

modules (if present) as indicated in

Table A

through

Table D

starting on

page 30

.

Measurement Points for Forward and Reverse Diode Tests

~.0L

+

-

~0.5V

+

-

Forward biased
test on
PN-junction

Reverse biased
test on
PN-junction

DANGER

DANGER

DC BUS CONDUCTORS AND CAPACITORS

OPERATE AT HIGH VOLTAGE. REMOVE POWER

AND WAIT 5 MINUTES BEFORE SERVICING

DANGER

DANGER

DC BUS CONDUCTORS AND CAPACITORS

OPERATE AT HIGH VOLTAGE. REMOVE POWER

AND WAIT 5 MINUTES BEFORE SERVICING

Cat No.

1234567890-*

FIELD INSTALLED OPTIONS:

FIELD INSTALLED OPTIONS:

DC- DC+

DC- DC+

1L1

1L2

1L3

2L1

2L2

2L3

1U/T1

1V/T2

1W/T3

2U/T1

2V/T2

2W/T3

Power Structure #1

Power Structure #2