PowerFlex® 700S and 700H Frame 12 DC Bus Connector Kit

5

Publication PFLEX-IN022A-EN-P

Step 2: Prepare the
Existing Enclosure

1. Optionally, open the enclosure doors and remove the bolts and washers that

secure the AC input power cables to terminals 1L1, 1L2 and 1L3, and 2L1,
2L2 and 2L3 at the top of the drive and secure the cables to the top of the
enclosure.

2. Remove the screws that secure the existing air flow restriction plate to the

left enclosure frame and remove the plate. Retain the screws for reuse with
the new air flow plate.

ATTENTION: A hazard of personal injury and/or equipment
damage exists if an object falls into an opening in the top of the
power structures. Precautions should be taken while installing this
kit to ensure that objects do not fall into one of these openings.

ATTENTION: A hazard of personal injury and/or equipment
damage exists if the AC input power cable insulation becomes
damaged and/or fails. Precautions should be taken to ensure that the
insulation on the AC input power cables is not damaged during bus
bar installation and drive operation. Thoroughly inspect the cable
insulation to verify that no damage has occurred after the bus bar kit
has been installed.

DANGER

DC BUS CONDUCTORS AND CAPACITORS

OPERATE AT HIGH VOLTAGE. REMOVE POWER

AND WAIT 5 MINUTES BEFORE SERVICING

DANGER

DANGER

DC BUS CONDUCTORS AND CAPACITORS

OPERATE AT HIGH VOLTAGE. REMOVE POWER

AND WAIT 5 MINUTES BEFORE SERVICING

FIELD INSTALLED OPTIONS:

FIELD INSTALLED OPTIONS:

FIELD INSTALLED OPTIONS:

2L1, 2L2, 2L3

1L1, 1L2, 1L3

Air flow plate

located

between

enclosures