Rockwell Automation 20D PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit User Manual

Page 32

Advertising
background image

Publication PFLEX-IN022A-EN-P

32

PowerFlex® 700S and 700H Frame 12 DC Bus Connector Kit

5. Complete the conductivity test between the left and right power structures as

indicated in

Table I

below.

Important: If the drive fails any of these measurements, verify that you have

properly connected the bus bar kit using the correct terminals.

6. Complete the conductivity test on the DC bus as indicated in

Table J

below.

Important: If the drive fails any of these measurements, refer to the

Hardware Service Manual for PowerFlex 700S and 700H Drives
(Frame 12), publication PFLEX-TG004…, for troubleshooting
information.

7. Complete the conductivity test on the DC bus to drive chassis ground as

indicated in

Table K

below.

Important: If the drive fails any of these measurements, refer to the

Hardware Service Manual for PowerFlex 700S and 700H Drives
(Frame 12), publication PFLEX-TG004…, for troubleshooting
information.

Table I Conductivity Test Between Left and Right Power Structures

Meter Leads

Nominal meter reading

+

-

+ DC Bus (Left)

+ DC Bus (Right)

Meter should read 0.000

– DC Bus (Left)

– DC Bus (Right)

Table J Conductivity Test on DC Bus

Meter Leads

Nominal meter reading

+

-

+ DC Bus

– DC Bus

Meter should gradually rise until leads
are removed. Note: Meter may fall and
transition through zero before rising.

– DC Bus

+ DC Bus

Table K Conductivity Test on DC Bus to Drive Chassis Ground

Meter Leads

Nominal meter reading

+

-

+ DC Bus

Chassis
Ground

Meter should display “.0L” (zero load).

– DC Bus

Chassis
Ground

Chassis
Ground

+ DC Bus

Chassis
Ground

– DC Bus

Advertising
This manual is related to the following products: