As indicated in, Table a, Table d – Rockwell Automation 20D PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit User Manual
Page 30: Starting on

30
PowerFlex® 700S and 700H Frame 12 DC Bus Connector Kit
Important: If the drive fails any of these measurements, replace the
appropriate Rectifying Module. Refer to the Hardware Service
Manual for PowerFlex 700S and 700H Drives (Frame 12),
publication PFLEX-TG004…, for details.
Table A Forward Biased Diode Tests - Rectifying Module for Power Structure #1
Meter Leads
Nominal meter reading
-
+
DC+/R+
(1)
(1)
If the drive does not contain the brake chopper option, the DC+/R+
terminal will be labeled DC+.
1L1
Meter should beep once and value
should gradually rise to about 0.5V
DC+/R+
1L2
DC+/R+
1L3
1L1
DC-
1L2
DC-
1L3
DC-
Table B Forward Biased Diode Tests - Rectifying Module for Power Structure #2
Meter Leads
Nominal meter reading
-
+
DC+/R+
(1)
(1)
If the drive does not contain the brake chopper option, the DC+/R+
terminal will be labeled DC+.
2L1
Meter should beep once and value
should gradually rise to about 0.5V
DC+/R+
2L2
DC+/R+
2L3
2L1
DC-
2L2
DC-
2L3
DC-
Table C Reverse Biased Diode Tests - Rectifying Module for Power Structure #1
Meter Leads
Nominal meter reading
+
-
1L1
DC-
Meter should display “.0L” (zero load)
1L2
DC-
1L3
DC-
DC+/R+
(1)
(1)
If the drive does not contain the brake chopper option, the DC+/R+
terminal will be labeled DC+.
1L1
DC+/R+
1L2
DC+/R+
1L3
Table D Reverse Biased Diode Tests - Rectifying Module for Power Structure #2
Meter Leads
Nominal meter reading
+
-
2L1
DC-
Meter should display “.0L” (zero load)
2L2
DC-
2L3
DC-
DC+/R+
(1)
(1)
If the drive does not contain the brake chopper option, the DC+/R+
terminal will be labeled DC+.
2L1
DC+/R+
2L2
DC+/R+
2L3