Trigger isolation jumpers, Normal operation versus monitor mode – Rockwell Automation 44887-PUB, 44887 Enwatch User Manual

Page 13

Advertising
background image

Publication GMSI10-UM031C-EN-E - January 2009

Installing the Enwatch 9

Trigger Isolation Jumpers

Four jumpers, JP17 to JP20, are sited on the board to enable the four trigger
inputs to be isolated or non-isolated. Non-isolated means the common of the
trigger input can be connected to the common of the Enwatch unit. With a
jumper removed, the trigger is isolated. Table 1.13 summarizes the jumper
positions.

Normal Operation versus Monitor Mode

The Enwatch unit incorporates an on-board monitor program for checking
the unit and modifying the system’s IP address. Inserting a jumper in JP21
enters into monitor mode.

Table 1.13 Jumper positions

Mode

Jumper

External trigger 1 isolated

JP17 Out

External trigger 1 non-isolated

JP 17 In

External trigger 2 isolated

JP18 Out

External trigger 2 non-isolated

JP18 In

External trigger 3 isolated

JP19 Out

External trigger 3 non-isolated

JP19 In

External trigger 4 isolated

JP20 Out

External trigger 4 non-isolated

JP20 In

IMPORTANT

If an external sensor is to be used that is powered from pin
1 of J3, J4, J5 or J6, then the jumper corresponding to the
trigger channel must be inserted to provide a ground return
path for the sensor power.

Table 1.14 Normal vs. monitor mode

Mode

Jumper J21

Normal

Out

Monitor

In