Rockwell Automation 44887-PUB, 44887 Enwatch User Manual

Page 26

Advertising
background image

Publication GMSI10-UM031C-EN-E - January 2009

22 Installing the Enwatch

Sampling rate

64 to 51200 Hz by 1

Number of synchronous time averages

1, 2, 4, 8, 32 ... 32768

Sample length

Multiple of 256 bytes, maximum sample 32768 bytes if no trigger, 16384 bytes with
pre-trigger (not used in first version of Enwatch)

Filter settling time

HP 0.36 Hz 18 seconds
HP 2.67 Hz 3 seconds
HP 5.3 Hz 1.2 seconds
HP 23.8 Hz 0.3 seconds
Integrator HP 0.36 Hz 25 seconds
Integrator HP 2.67 Hz 8 seconds
Integrator HP 5.3 Hz 1.5 seconds
Integrator HP 23.8 Hz 0.8 seconds
gSE 200 Hz 88 milliseconds
gSE 5 kHz 2 milliseconds
Core 0.7 seconds
Time constant of 0.03 seconds 300 milliseconds
Time constant of 0.006 seconds 60 milliseconds
Time constant of 0.0012 seconds 12 milliseconds
Time constant of 0.00024 seconds 3 milliseconds

Trigger delay

0-32768 samples. Emonitor always uses 0.

Trigger channel

1-4 channels, TTL input 5-20 V
Maximum combined trigger current (channels 1-4), not to exceed 100mA.

Gain control

X1, X10, X100, X1000, X5, X50, X500, X5000
Download X1 always. The Enwatch unit autoranges and returns back the current gain for
rescaling.

Anti-Alias filter

20 kHz, 2 kHz, 500 Hz, 100 Hz. This is read only. The Enwatch unit selects the proper filter.

Table 1.16 Enwatch measurement capabilities

Product Feature

Capability

FMAX

Sampling Rate

FMAX

Sampling Rate

25

64

2000

5120

50

128

3200

8192

100

256

4000

10240

200

512

5000

12800

400

1024

6400

16384

500

1280

8000

20480

800

2048

10000

25600

1000

2560

16000

40960

1600

4096

20000

51200