Chapter

1

Installing the Enwatch

This manual introduces you to the Allen Bradley Enwatch

®

unit. The manual

is intended for anyone who installs, tests, or configures the Enwatch hardware.
It does not cover using the Enwatch unit to collect data. For information on
collecting data with the Enwatch unit, refer to the Online Applications Guide
provided with your Emonitor

®

online system.

Introduction

Enwatch is a distributed network system providing 16 channels of analog
inputs together with 4 trigger channels. The unit includes signal conditioning
and analog to digital conversion. It allows you to connect 16 two-wire ICP or
other sensors into your Emonitor Online system. Each Enwatch unit is a
microprocessor-based system, complete with network controller that carries
out data acquisition tasks as directed by an Emonitor unload station. A typical
diagram for an Enwatch unit is shown in Figure 1.1, below.

Figure 1.1 Enwatch diagram

The Enwatch unit responds to all relevant network data exchanges as defined
by the Ethernet protocol using the UDP/IP standard. In addition, there is a
comprehensive on-board monitor program that can exercise all functions via
the on-board serial RS232 port.

ICP 1

ICP 2

ICP 16

15
:1

Bi

as
C
hec

k

HP Filters

Intergrator

Programable

Gain

Select

gSE

A to D

Converter

Watchdog

Micro-
processor

Clock

Generator

Flash

SRAM

RS-232

4:

1

Au
x

.

Power

Regulation

Ethernet

Controller

10Base-T

Programable

Anti-Alias

Filter

External Trig. 1 - Event

External Trig. 4

DC in

CHANNEL

M

u

lt

ip

le

x

e

r