Installing the Enwatch 23

gSE time constant

0.03, 0.006, 0.0012, 0.00024 seconds, the default is 0.03 seconds
if FMAX > 350Hz set to 0.00024 seconds
else if FMAX > 150 Hz set to 0.0012 seconds
else if FMAX > 37.5 Hz set to 0.006 seconds

If the measurement is overall only (no spectrum) then set to 0.03 seconds.

Integrator

One level of hardware integration

The hardware has a gain factor of:
2.67/f for the 0.36 Hz and the 2.67 Hz filter ranges (INTHI = 0)
38.9/f for the 5.3 Hz and 23.7 Hz filter ranges (INTHI = 1)

To convert from g->ips:
Velocity (ips peak) = [integrator output (volts peak)] x [1 / (gain factor)] x [accel scale factor
(g peak / mv peak)] x [61.24 / frequency]

Sample sequence allowed

4096 - one sample sequence uses one configuration table

Configuration tables

128 - one measurement point uses one table so total will be 128 points

Storage overhead

18 bytes per allocation

Flash memory lifetime

100,000 writes

Total available memory

640 Kilobytes

HOST software support (Emonitor)

Window types: Hanning, Hamming, Rectangular, Kaiser Bessel, Flattop

Number of lines

100, 200, 400, 800, 1600, 3200

Number of averages

1-99

Bias voltage reading

When you define a process measurement of DC in Emonitor, the Enwatch unit reads the
transducer bias voltage.
24V means open circuit, 10V is OK.

Table 1.16 Enwatch measurement capabilities