3: Install and Wire The Drive

DANGER

ONLY QUALIFIED ELECTRIĆ

CAL PERSONNEL FAMILIAR

WITH THE CONSTRUCTION

AND OPERATION OF THIS

EQUIPMENT AND THE HAZĆ

ARDS INVOLVED SHOULD

INSTALL, ADJUST, OPERATE

AND/OR

SERVICE

THIS

EQUIPMENT.

READ AND

UNDERSTAND THIS MANUAL

IN ITS ENTIRETY BEFORE

PROCEEDING. FAILURE TO

OBSERVE THIS PRECAUTION

COULD RESULT IN SEVERE

BODILY INJURY OR LOSS OF

LIFE.

DANGER

THE USER IS RESPONSIBLE

FOR CONFORMING TO THE

NATIONAL

ELECTRICAL

CODE (NEC) AND ALL OTHER

APPLICABLE LOCAL CODES

WITH RESPECT TO WIRING

PRACTICES,

GROUNDING,

DISCONNECTS, AND OVERĆ

CURRENT PROTECTION ARE

OF

PARTICULAR

IMPORĆ

TANCE.

FAILURE TO OBĆ

SERVE THIS PRECAUTION

COULD RESULT IN SEVERE

BODILY INJURY OR LOSS OF

LIFE.

DANGER

THIS EQUIPMENT IS AT LINE

VOLTAGE WHEN AĆC POWER

IS CONNECTED. DISCONĆ

NECT AND LOCKOUT ALL

UNGROUNDED

CONDUCĆ

TORS OF THE AĆC POWER

LINE. FAILURE TO OBSERVE

THIS PRECAUTION COULD

RESULT IN SEVERE BODILY

INJURY OR LOSS OF LIFE.

General

This Section outlines the

procedures that are to be followed

to properly install the MinPak Plus

SingleĆPhase DĆC Drive. Refer to

Figure3Ć2 for mounting dimensions.

Install the Controller -

Panel Layout

The controller is designed as a wall

or panel mount unit and must be

hung within 10_ of vertical with the

rear of the chassis firmly bolted to

themounting surface. Do not mount

thechassis in a horizontal position.

Reference figures 3Ć1, 3Ć1A and

3Ć1B for minimum mounting

distances and/or mounting

orientations.
Leave 2 inches (50 mm) clearance

around the 3 unhinged sides of the

chassis. This area must remain

unobstructed for proper air

circulation through theheat sink. Do

not placethecontroller directly in a

corner, leave at least 8 inches (200

mm) from thetop and 6 inches (150

mm) from thebottom of thecabinet.
Regardless of the above placement

guidelines, the user is responsible

for ensuring that the Controller's

ambient specification of 0 to 55_C is

met. Relative humidity must be kept

within 5% to 95% without

condensation.

Figure 3Ć1. Enclosure Mounting

Minimum Distances

Figure 3Ć1A. Open Panel Minimum

Mounting Distances

Figure 3Ć1B. Mounting

Orientations