Rockwell Automation MinPak Plus DC Drive User Manual User Manual

Page 43

Advertising
background image

5:12

Done

A

Fixed?

See Note #1

Replace

regulator board

Yes

No

Is reference

voltage

present?

Check reference voltage beĆ

tween pins 26 and 57 (ComĆ

mon).

Is reference

voltage

present?

Check to see if jumper J4 on

the regulator board has been

cut or removed.

B

Is

voltage

present?

Replace

regulator board

Done

Fixed?

See Note #1

Yes

No

Replace control

transformer

Done

Fixed?

Yes

No

No

Yes

Check DĆC Voltage between

terminals 28 and 20 with MAX

speed pot turned fully clockĆ

wise (Approx. 11.2 VDC).

Replace Remote

Operator Buffer Kit

Done

Fixed?

Yes

No

Is

voltage

present?

See Note #1

C

No

Yes

No

Yes

Note #1: Contact local sales/service office.

Yes

No

From

previous

page

From

previous

page

D

Go to

next page

Go to next

two pages

DANGER

SOME OF THE FOLLOWING CHECKS AND PROCEDURES REQUIRE THE POWER TO BE ON. EXERCISE

EXTREME CARE AS HAZARDOUS VOLTAGE EXISTS. FAILURE TO OBSERVE THIS PRECAUTION COULD

RESULT IN SEVERE BODILY INJURY OR LOSS OF LIFE.

Figure 5Ć8. M" Contactor PicksĆUp But Motor Does Not Run. (Continued)