background image

4:6

See Figure 4Ć4 and Figure 4Ć5 for

zero speed circuit configurations.
Controllers with P/N 57100

regulators that do not have a J10

jumper can achieve zero minimum

speed by turning the minimum

speed rheostat fully

counterĆclockwise. Controllers that

have a J10 jumper can achieve zero

minimum speed by moving the J10

jumper between K71 and K72, and

turning the MIN SPD rheostat fully

counterĆclockwise. (See Figure 4Ć5.)

to

Figure 4Ć4. Controller with J10 Jumper in Zero Speed Circuit

NOTE: A 3 to 4 megohm resistor

between terminals 319 and 71 can

be used if some indication of speed

is still detected after zero speed is

commanded. (See Figure 4Ć4).

Figure 4Ć5. Zero Minimum Speed Correction