Configurable Monitoring Safety Relay with DeviceNet™ Communications

Chapter 2: Device Parameters

10

MSR312-UM001B-EN-P

Parameters 30…32—Group Status (read only)

Group 1…3 Status

These parameters indicates if any of the MSR320P Input Modules assigned to Groups 1, 2, or 3 have an interrupted input. The
meaning of the values are:

Parameters 33…35—Feedback (Monitoring) Loop Status (read only)

Group 1…3 EDM Status

The Feedback Loop Status parameters reflect the status of the EDM circuits at terminals Y11, Y12, and Y13. The meaning of
the values are:

Parameters 36…38—Group State (read only)

Group 1…3 State

The Group State parameters reflects the status of the Group 1, 2, and 3 output modules. The meaning of the values are:

Parameter 39—Group Reset State (read only)

The MSR312P can be set up for four different reset modes. These modes are configured by wiring only; they cannot be
changed by software. The setting are made at the terminals Y40, Y41, and Y42

Value

Meaning

00
01

Inputs are active—OK
At least one input assigned to the Group is interrupted.

Value

Meaning

00
01

Feedback Loop Open
Feedback Loop Closed

Value

Meaning

00
01
10

Output is off
Output is ready for reset
Output is active

Parameter 39 value: XXXX0000

Jumper from Y40 to Y41 and Y42
Group 1, 2, and 3: Automatic Reset

Parameter 39 value: XXXX0001

Jumper from Y40 to Y41
Group 1 and 2: Monitored Manual Reset
Group 3: Automatic Reset

Parameter 39 value: XXXX0010

Jumper from Y40 to Y42
Group 1 and 2: Automatic Reset
Group 3: Monitored Manual Reset

Parameter 39 value: XXXX0011

No Jumpers
Group 1, 2, and 3 Monitored Manual Reset