Configurable Monitoring Safety Relay with DeviceNet™ Communications

Chapter 3: Quick Start Guide

20

MSR312-UM001B-EN-P

Step 3. Set up I/O parameters for the MSR312P.

Verify the Strobed and Polled boxes are unchecked. Check the “Change of State/Cyclic” box. Set the Input Size to 2 and the
Output Size to 1. We knew the I/O sizes from the parameter help within the MSR312P Parameter (103, 104, 105). Select an
appropriate Heartbeat Rate. (Default is ok) Click OK.