Chapter 7: Off-Line Node Recovery

44

MSR312-UM001B-EN-P

Chapter 7: Off-Line Node Recovery

Overview

The MSR312P base module is equipped with a function known as Off-Line Node Recovery. Off-Line Node Recovery is used
mainly to commission a device on a network. When a new product is put on the network, it is at a default address of Node 63. If
multiple units are placed on a network without first using node commissioning to change the node address a duplicate MAC ID
error occurs. This means that more than one device is located at the same node address and only one of them is allowed online.
Off-Line Node Recovery now allows you to recover the faulted devices and change the node address. This is a powerful tool
because multiple nodes can be put on the network on installation and recovered one at a time without having to continually reset
the network. The following section will walk through a sample recovery.

Note: If the MAC ID is set through the rotary switches, Off-Line Node Recovery will not be able to recover the faulted device

because it cannot change the node address.

Sample Recovery

This example has placed two MSR312P base modules on a network at the same node address 63.

From RSNetWorx, click the Single Pass Browse button. The following message will appear in the message box at the bottom of
the screen.

Select Faulted Address Recovery Wizard from the Tools menu.

Click the “Next” button.