Configurable Monitoring Safety Relay with DeviceNet™ Communications

Chapter 2: Troubleshooting and Maintenance

8

MSR312-UM001B-EN-P

Chapter 2: Troubleshooting and Maintenance

Using the Status LED

Using the Mod/Net Status LED

Function

Status LED

Group 1-2-3 LEDs

Power up / normal operation

Continuous on: green

Internal fault

Continuous on: red

Entering configuration mode

1 flash: red

Input switch fault or reset switch closed during power up

2 flashes: red

Configuration change during operation

3 flashes: red

Current configuration not as stored on EEPROM

4 flashes: red

At least one muting lamp and one reserve lamp defective

5 flashes: red

Invalid switch settings of input modules

6 flashes: red

Invalid reset configuration (Y41, Y42, S34 terminal jumpers)

7 flashes: red

Input terminal block not (or improperly) plugged in

8 flashes: red

Group output active

Continuous on: green

Group ready

Blinking: green

At least one input corresponding to the output group is faulty

Continuous on: red

A feedback (EDM) loop of the output group is open, or no input is assigned to the group —

Off

Mod/Net State

LED

Indication

Not powered/not on-line

Off

Device is not on-line. Device has not completed the Dup MAC ID test. Device may not
be powered.

Device operational and on-
line, connected

Solid green

Device is operating in a normal condition and is on-line with connections in the
established state. For Group 2 only, the device is allocated to a master. For a UCMM
capable device it means that the device has one or more established connections.

Device operational and on-
line, not connected, or
device on-line and needs
commissioning

Flashing green

Device is on-line with no connections in the established state. Device has passed the
Dup MAC ID test, is on-line, but has no established connections to other nodes. For a
Group 2 Only device, the device is not allocated to a master. For a UCMM capable
device it means that the device has no established connections. Configuration
missing, incomplete or incorrect.

Minor fault and/or
connection time-out

Flashing red

Recoverable fault and/or one or more I/O connections are in the timed-out state.
Recoverable faults include:

Failed Power Supply power-up test.

Faulted 24V DC, Out2, Out3.

Critical fault or critical link
failure

Solid red

Device has an unrecoverable fault and may need replacing. Device has detected an
error that has rendered it incapable of communication on the network (Dup MAC
failure or Bus Off).

Communication faulted and
received an identify comm
fault request - long protocol

Flashing red and
green

A specific communcation faulted device. the device has detected a network access
error and is in the communcation faulted state. The device has subsequently received
and accepted an identify communcation faulted request - long protocol message.