Configurable Monitoring Safety Relay with DeviceNet™ Communications

Chapter 7: Off-Line Node Recovery

MSR312-UM001B-EN-P

45

If there are multiple faulted devices, they will show up in the list. Devices are identified by the DeviceNet serial number that is
unique to every product. The serial number for the MSR312P base module can be located on the name plate or inside the
product. Click the “Next” button.

If there are multiple faulted units, you can verify which unit you are recovering by flashing the Mod/Net Status LED. To do this
click “Flash LED.” The LED will flash between red and green. Click “00” under New Address to change the new address.