Rockwell Automation 440R MSR312 Configurable Monitoring Safety Relay w/DeviceNet Communications User Manual

Page 52

Advertising
background image

Configurable Monitoring Safety Relay with DeviceNet™ Communications

Chapter 8: DeviceNet Classes and Objects

52

MSR312-UM001B-EN-P

Instance 171 (20 Point Input w/Single Status Bit)

Note: Response time is assembly dependant, and will vary depending upon the number of input modules attached to the

system. The response time will be longest with ten input modules attached.

Class Code 0x0005: Connection Object

No class attributes will be supported for the Connection Object. Five instances of the Connection Object will be supported.
Instance 1 will be the explicit message connection, instance 2 will be the polled IO connection, and instance 4 will be the COS/
Cyclic IO connection. Instance 1 is the Predefined Group 2 Connection Set Explicit Message Connection. The following
instance 1 attributes will be supported:

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Input 4b State Input 4a State Input 3b State Input 3a State Input 2b State Input 2a State Input 1b State Input 1a State

1

Input 8b State Input 8a State Input 7b State Input 7a State Input 6b State Input 6a State Input 5b State Input 5a State

2

Device Fault

Reserved

Reserved

Reserved

Input 10b

State

Input 10a

State

Input 9b State Input 9a State

Input Modules

Response time

One

16.2mS

Ten

56.4mS

Attribute ID Access Rule

Name

Data Type

Value

1

Get

State

USINT

0 = non-existent 1 = configuring 3 =
established 4 = timed out

2

Get

Instance Type

USINT

0 = Explicit Message

3

Get

Transport Class Trigger

BYTE

0x83 — Server, Transport Class 3

4

Get

Produced Connection ID

UINT 10xxxxxx011

xxxxxx = node

address

5

Get

Consumed Connection ID

UINT 10xxxxxx100

xxxxxx = node

address

6

Get

Initial Comm Characteristics

BYTE

0x22

7

Get

Produced Connection Size

UINT

0x61

8

Get

Consumed Connection Size

UINT

0x61

9

Get/Set

Expected Packet Rate

UINT

In milliseconds

12 (OC

hex

)

Get

Watchdog Action

USINT

01 = auto delete 03 = deferred
delete

13 (OD

hex

)

Get

Produced Connection Path Length

UINT

0

14 (OE

hex

)

Get

Produced Connection Path

EPATH

Empty

15 (OF

hex

)

Get

Consumed Connection Path Length UINT

0

16 (10

hex

)

Get

Consumed Connection Path

EPATH

Empty

Advertising