Ventilation

The ventilation openings must fulfill the requirements set by the selected IP class.
The examples in this manual apply to protection class IP21.

Table 9

contains the

minimum required air opening dimensions. Refer to

Figure 7

for the location of

the openings as indicated in the table below.

Table 9 - IP21 Ventilation Opening Minimum Requirements

Figure 7 - Enclosure Ventilation Example

Opening

Purpose

Enclosure Width

(1)

(1) Refer to Enclosure Requirements on page

9

for the required enclosure widths for each drive frame size.

600 mm (23.6 in.)

800 mm (31.5 in.)

Area for cool air intake

130,050 mm

2

195,075 mm

2

Area for hot air exhaust

70,000 mm

2

105,000 mm

2

A

B

600 mm

(23.6 in.)

A

B

800 mm

(31.5 in.)

A

B