PowerFlex 700S and 700H Frames 10...14 IP00, NEMA/UL Open Power Structures

Output Power Wiring

Frame 12 and 14 drives utilize two parallel power structures, and therefore have
two sets of output power terminals. You must connect the motor to both sets of
output power terminals.

Figure 36 - Frame 12 and 14 Output Power Wiring Example

IMPORTANT

Parallel wiring must have the same cable dimensions, type and routing. Non-
symmetrical wiring may cause unequal loading between the converters and
reduce the drive’s ability to deliver current to the motor. Refer to

Figure 36

below for details.

IMPORTANT

The minimum cable length for parallel motor cables from the drive to the point
where the cables connect is 5m (16.4 ft.). Join the parallel cables at the motor
end (not the drive end). Or, install a reactor on the output of each power
module with a minimum of 5 μH prior to joining the parallel cables at the
motor end. Refer to

Figure 36

below for details.

1T1

1T2

1T3

2T1

2T2

2T3

PE

PE

Motor Frame

Motor

5 m (16.4 ft)

minimum