Heat Dissipation

The efficiency of the frequency converter is a function of switching frequency,
operating frequency and load. Based on this information, heat dissipation can be
calculated at a certain operating point. For most cases the following general
formula based on frequency converter load can be used to estimate the heat
dissipation of the power structure:

P

loss

(kW) = P

mot

(kW) x 0.025

Watts Loss

Table 10 - 400 and 480V AC Input Drive Watts Loss Data

Table 11 - 600 and 690V AC Input Drive Watts Loss Data

Drive
Catalog
Number

(1)

(1) Refer to rating columns for catalog number explanation.

Output
Amps

(2)

(2) These drives have dual current ratings; one for normal duty applications, and one for heavy duty (in parenthesis). The drive may be

operated at either rating.

480V AC Input (20xD)

(3)

400V AC Input (20xC)

(3)

(3) x = “D” for PowerFlex 700S and “C” for PowerFlex 700H.

Fram

e

Watts Loss

ND HP

HD HP

ND kW

HD kW

20x385N

385 (300)

300

250

200

160

10

4320

20xy460N

460 (385)

350

300

250

200

10

5335

20xy500N

500 (420)

450

350

250

250

10

5921

20xy590N

590 (520)

500

450

315

250

11

6620

20xy650N

650 (590)

500

500

355

315

11

7538

20xy730N

730 (650)

600

500

400

355

11

8312

20xy820N

820 (730)

700

600

450

400

12

9201

20xy920N

920 (820)

800

700

500

450

12

10670

20xy1K0N

1030 (920)

900

800

560

500

12

11729

20xy1K1N

1150 (1030)

1000

900

630

560

13

13801

20xy1K3N

1300 (1150)

1200

1000

710

630

13

15077

20xy1K4N

1450 (1200)

1250

1000

800

710

13

16511

20xy1K7N

1770 (1600)

1500

1400

1000

900

14

24800

20xy2K1N

2150 (1940)

1900

1700

1200

1100

14

29900

20xy2K7N

2700 (2300)

2300

2000

1600

1300

14

39680

Drive
Catalog
Number

(1)

(1) Refer to rating columns for catalog number explanation.

Output
Amps

(2)

(2) These drives have dual current ratings; one for normal duty applications, and one for heavy duty (in parenthesis). The drive may be

operated at either rating.

600V AC Input (20xE)

(3)

690V AC Input (20xF)

(3)

(3) x = “E” for PowerFlex 700S and “F” for PowerFlex 700H.

Fram

e

Watts Loss

ND HP

HD HP

ND kW

HD kW

20xy261N

261 (208)

250

200

250

200

10

4206

20xy325N

325 (261)

350

250

315

250

10

4751

20xy385N

385 (325)

400

350

355

315

10

5527

20xy416N

416 (325)

450

350

400

315

10

5622

20xy460N

460 (385)

450

400

450

355

11

6345

20xy502N

502 (460)

500

450

500

450

11

6925

20xy590N

590 (502)

600

500

560

500

11

7539

20xy650N

650 (590)

700

650

630

560

12

9502

20xy750N

750 (650)

800

700

710

630

12

10570

20xy820N

820 (750)

900

700

800

630

12

11082

20xy920N

920 (820)

1000

900

900

800

13

12690

20xy1K0N

1030 (920)

1100

1000

1000

900

13

15907

20xy1K1N

1180 (1030)

1300

1100

1100

1000

13

17306

20xy1K5N

1500 (1300)

1600

1400

1500

1300

14

22500

20xy1K9N

1900 (1500)

2000

1600

1800

1500

14

28500

20xy2K2N

2250 (1900)

2400

2000

2000

1800

14

33400