Table 14 - 600V AC Input Protection Devices

Drive Catalog
Number

Fram

e

HP Rating

Input
Ratings

Dual Element Time Delay Fuse

Non-Time Delay Fuse

Bussmann Style Semi-
Conductor Fuse

Circuit
Breaker

(6)

Motor Circuit
Protector

(8)

ND

HD

Amps

Min.

(3)

Max.

(4)

Min.

(3)

Max.

(4)

Max

(7)

Max.

20xE261

10

250

252

325

575

325

775

170M5813

700

350

200

201

275

450

275

600

170M5813

600

300

20xE325

10

350

314

400

725

400

950

170M5813

900

450

250

252

325

575

325

775

170M5813

750

400

20xE385

10

400

372

475

850

475

1100

170M5813

1100

500

350

314

400

725

400

950

170M5813

900

450

20xE416

10

450

402

525

900

525

1200

170M5813

1200

550

350

314

400

725

400

950

170M5813

900

450

20xE460

11

500

444

575 (1 per phs)
300 (2 per phs)

1000

575 (1 per phs)
300 (2 per phs)

1300

170M8547

1300

600

400

372

475 (1 per phs)
250 (2 per phs)

850

475 (1 per phs)
250 (2 per phs)

1100

170M8547

1100

500

20xE502

11

500

485

625 (1 per phs)
325 (2 per phs)

1100

625 (1 per phs)
325 (2 per phs)

1500

170M8547

1500

650

500

444

575 (1 per phs)
300 (2 per phs)

1000

575 (1 per phs)
300 (2 per phs)

1300

170M8547

1300

600

20xE590

11

600

570

725 (1 per phs)
375(2 per phs)

1300

725 (1 per phs)
375(2 per phs)

1700

170M5813

1700

800

500

485

625 (1 per phs)
325 (2 per phs)

1100

625 (1 per phs)
325 (2 per phs)

1500

170M5813

1500

700

20xE650

12

700

628

800 (1 per phs)
400 (2 per phs)

1400

800 (1 per phs)
400 (2 per phs)

1900

170M5813

1900

900

650

570

725 (1 per phs)
375 (2 per phs)

1300

725 (1 per phs)
375 (2 per phs)

1700

170M5813

1700

800

20xE750

12

800

724

950 (1 per phs)
475 (2 per phs)

1600

950 (1 per phs)
475 (2 per phs)

2200

170M5813

2200

1000

700

628

800 (1 per phs)
400 (2 per phs)

1400

800 (1 per phs)
400 (2 per phs)

1900

170M5813

1900

900

20xE820

(1)

12

900

792

1000 (1 per phs)
500 (2 per phs)

1800

1000 (1 per phs)
500 (2 per phs)

2400

170M5813

2400

1100

700

628

800 (1 per phs)
400 (2 per phs)

1400

800 (1 per phs)
400 (2 per phs)

1900

170M5813

1900

900

20xE920

13

1000

888

1200 (1 per phs)
600 (2 per phs)

2000

1200 (1 per phs)
600 (2 per phs)

2700

170M6466

(5)

2700

1200

900

792

1000 (1 per phs)
500 (2 per phs)

1800

1000 (1 per phs)
500 (2 per phs)

2400

170M6466

(5)

2400

1100

20xE1K0

13

1100

994

1300 (1 per phs)
650 (2 per phs)

2300

1300 (1 per phs)
650 (2 per phs)

3000 170M6466

(5)

3000

1300

1000

888

1200 (1 per phs)
600 (2 per phs)

2000

1200 (1 per phs)
600 (2 per phs)

2700

170M6466

(5)

2700

1200

20xE1K1

13

1300

1139

1500 (1 per phs)
750 (2 per phs)

2600

1500 (1 per phs)
750 (2 per phs)

3500

170M6466

(5)

3500

1500

1100

994

1300 (1 per phs)
650 (2 per phs)

2200

1300 (1 per phs)
650 (2 per phs)

3000

170M6466

(5)

3000

1300

20xE1K5

14

1000

1448

1900 (1 per phs)
650 (3 per phs)

3300

1900 (1 per phs)
650 (3 per phs)

4500

170M6466

4500

1900

900

1255

1600 (1 per phs)
550 (3 per phs)

2900

1600 (1 per phs)
550 (3 per phs)

3900

170M6466

3900

1700

20xE1K9

(2)

14

1100

1834

2300 (1 per phs)
800 (3 per phs)

4200

2300 (1 per phs)
800 (3 per phs)

5700

170M6466

5700

2400

1000

1448

1900 (1 per phs)
650 (3 per phs)

3200

1900 (1 per phs)
650 (3 per phs)

4500

170M6466

4500

1900

20xE2K2

(2)

14

1200

2172

2800 (1 per phs)
950 (3 per phs)

5000

2800 (1 per phs)
950 (3 per phs)

6700

170M6466

6700

2900

1100

1834

2300 (1 per phs)
800 (3 per phs)

4200

2300 (1 per phs)
800 (3 per phs)

5700

170M6466

5700

2400

(1)

20DE820 drives (ND) are only capable of producing 95% of starting torque under 10 Hz.

(2)

Not available with 700S Control.

(3)

Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.

(4)

Maximum protection device size is the highest rated device that supplies drive protection.

(5)

These fuses and disconnect are supplied with AC input NEMA/UL Type 1 drives.

(6)

Inverse time breaker. Ratings shown are maximum.

(7)

Maximum allowable rating by US NEC. Exact size must be chosen for each installation.

(8)

Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.