PowerFlex 700S and 700H Frames 10...14 IP00, NEMA/UL Open Power Structures

Frames 13 and 14

To facilitate ease of service, it is recommended that the power structure be
mounted on support rails. Fasten the rails to the sides of the enclosure at
distances “B” (from the top) and “C” (from the bottom) shown in

Figure 11

.

Leave a space (“A”) between the power structure and top of the enclosure for
internal cooling air flow. Space between the enclosures is not required.

The power structure should be secured to the rear of the enclosure as shown by
installing two rails on the rear wall of the enclosure at appropriate levels. Refer to
the dimension drawings in Component Dimensions beginning on page

53

for

more details.

Figure 12 - Mounting Dimensions - Frames 13 and 14

Frame

Dimensions - mm (in.)
A

(1)

(1) Minimum distance from the top of the enclosure; this space is required for the DC busbars.

B

C

(2)

(2) Dimension if the AC choke is installed at the bottom of the enclosure. If the choke is installed in another location, the distance must

be greater than 300 mm (11.8 in.).

13 and 14

175 (6.9)

1050 (41.3)

600 (23.6)