Enclosure requirements – Rockwell Automation 20D PowerFlex 700S/700H Frames 10...14 IP00, NEMA/UL Open Power Structures User Manual

Page 9

Advertising
background image

Rockwell Automation Publication PFLEX-IN020C-EN-P - July 2013

9

PowerFlex 700S and 700H Frames 10...14 IP00, NEMA/UL Open Power Structures

Enclosure Requirements

The following enclosure specifications must be met for proper installation.

Table 6 - Frames 10…12

Table 7 - Frame 13

Table 8 - Frame 14

Specification

Frame 10

Frame 11

Frame 12

Width

600 mm (23.6 in.) Minimum

800 mm (31.5 in.) Minimum 1200 mm (47.2 in.) Minimum

Depth

Minimum 600 mm (23.6 in.) or a minimum of 490 mm (19.3 in.) if the control frame is
installed in a position other than the front of the power structure.

Height

Minimum 1800 mm (70.9 in.) if the AC choke is installed beneath the power structure,
otherwise a minimum of 1500 mm (59.1 in.).

Weight

Enclosure must be able to support the total equipment weight stated if the power structure
and AC choke are installed in the same enclosure. Refer to the PowerFlex 700H and 700S AC
Drive, Frames 9…14 Installation Instructions, publication

PFLEX-IN006

, for component

weights.

Construction

According to EN60439-1

Ventilation

See Airflow and Ventilation Requirements on page

13

.

Specification

Frame 13

(1)

(1) Refer to Frame 13 and 14 Component/Enclosure Configurations on page

11

for more information.

2 NFE Converters

3 NFE Converters

DC Input

Width

Enclosure A:
600 mm (23.6 in.) min
Enclosure B:
800 mm (31.5 in.) min

Enclosures A and B:
800 mm (31.5 in.) min

Enclosure A:
800 mm (31.5 in.) min

Depth

Minimum 600 mm (23.6 in.) is required to accommodate the depth of the inverter units.

Height

2200 mm (86.6 in.)

Weight

Enclosure must be able to support the total equipment weight stated if the power structure and AC
choke are installed in the same enclosure. Refer to the PowerFlex 700H and 700S AC Drive, Frames
9…14 Installation Instructions, publication

PFLEX-IN006

, for component weights.

Construction

According to EN60439-1

Ventilation

See Airflow and Ventilation Requirements on page

13

.

Specification Frame 14

(1)

(1) Refer to Frame 13 and 14 Component/Enclosure Configurations on page

11

for more information.

3 NFE Converters

4 NFE Converters

6 NFE Converters

DC Input

Width

Enclosures A, B and C:
800 mm (31.5 in.) Min.

Enclosures A and D:
600 mm (23.6 in.) Min.
Enclosure B and C:
800 mm (31.5 in.) Min.

Enclosures A, B, C, and D:
800 mm (31.5 in.) Min.

Enclosures A and B:
800 mm (31.5 in.) Min.

Depth

Minimum 600 mm (23.6 in.) is required to accommodate the depth of the inverter units.

Height

2200 mm (86.6 in.)

Weight

Enclosure must be able to support the total equipment weight stated if the power structure and AC
choke are installed in the same enclosure. Refer to the PowerFlex 700H and 700S AC Drive, Frames
9…14 Installation Instructions, publication

PFLEX-IN006

, for component weights.

Construction

According to EN60439-1

Ventilation

See Airflow and Ventilation Requirements on page

13

.