Rockwell Automation 20D PowerFlex 700S/700H Frames 10...14 IP00, NEMA/UL Open Power Structures User Manual

Page 28

Advertising
background image

28

Rockwell Automation Publication PFLEX-IN020C-EN-P - July 2013

PowerFlex 700S and 700H Frames 10...14 IP00, NEMA/UL Open Power Structures

Table 15 - 690V AC Input Protection Devices

Drive Catalog
Number

Fram

e

kW Rating

Input
Ratings

Dual Element Time Delay Fuse

Non-Time Delay Fuse

Bussmann Style Semi-
Conductor Fuse

Circuit
Breaker

(6)

Motor Circuit
Protector

(8)

ND

HD

Amps

Min.

(3)

Max.

(4)

Min.

(3)

Max.

(4)

Max.

(7)

Max.

20xF261

10

250

263

350

575

350

775

170M5813

750

350

200

210

275

450

275

600

170M5813

600

300

20xF325

10

315

327

425

725

425

950

170M5813

900

450

250

263

350

575

350

775

170M5813

750

400

20xF385

10

355

388

500

850

500

1100

170M5813

1100

500

315

327

425

725

425

950

170M5813

900

450

20xF416

10

400

419

525

900

525

1200

170M5813

1200

550

315

327

425

700

425

950

170M5813

900

450

20xF460

11

500

463

600 (1 per phs)
300 (2 per phs)

1000

600 (1 per phs)
300 (2 per phs)

1300

170M8547

1300

600

400

388

500 (1 per phs)
250 (2 per phs)

850

500 (1 per phs)
250 (2 per phs)

1100

170M8547

1100

500

20xF502

11

560

506

650 (1 per phs)
325 (2 per phs)

1100

650 (1 per phs)
325 (2 per phs)

1500

170M8547

1500

650

500

463

600 (1 per phs)
300 (2 per phs)

1000

600 (1 per phs)
300 (2 per phs)

1300

170M8547

1300

600

20xF590

11

580

594

750 (1 per phs)
375 (2 per phs)

1300

750 (1 per phs)
375 (2 per phs)

1700

170M5813

1700

800

500

506

650 (1 per phs)
325 (2 per phs)

1100

650 (1 per phs)
325 (2 per phs)

1500

170M5813

1500

700

20xF650

12

630

655

850 (1 per phs)
425 (2 per phs)

1400

850 (1 per phs)
425 (2 per phs)

1900

170M5813

1900

900

560

594

750 (1 per phs)
375 (2 per phs)

1300

750 (1 per phs)
375 (2 per phs)

1700

170M5813

1700

800

20xF750

12

710

756

950 (1 per phs)
475 (2 per phs)

1600

950 (1 per phs)
475 (2 per phs)

2200

170M5813

2200

1000

630

655

850 (1 per phs)
425 (2 per phs)

1400

850 (1 per phs)
425 (2 per phs)

1900

170M5813

1900

900

20xF820

(1)

12

800

826

1100 (1 per phs)
550 (2 per phs)

1800

1100 (1 per phs)
550 (2 per phs)

2400

170M5813

2400

1100

630

655

850 (1 per phs)
425 (2 per phs)

1400

850 (1 per phs)
425 (2 per phs)

1900

170M5813

1900

900

20xF920

13

900

927

1200 (1 per phs)
600 (2 per phs)

2000

1200 (1 per phs)
600 (2 per phs)

2700

170M6466

(5)

2700

1200

800

826

1100 (1 per phs)
550 (2 per phs)

1800

1100 (1 per phs)
550 (2 per phs)

2400

170M6466

(5)

2400

1100

20xF1K0

13

1000

1038

1300 (1 per phs)
650 (2 per phs)

2300

1300 (1 per phs)
650 (2 per phs)

3000

170M6466

(5)

3000

1300

900

927

1200 (1 per phs)
600 (2 per phs)

2000

1200 (1 per phs)
600 (2 per phs)

2700

170M6466

(5)

2700

1200

20xF1K1

13

1100

1189

1500 (1 per phs)
750 (2 per phs)

2600

1500 (1 per phs)
750 (2 per phs)

3500

170M6466

(5)

3500

1500

1000

1038

1300 (1 per phs)
650 (2 per phs)

2300

1300 (1 per phs)
650 (2 per phs)

3000

170M6466

(5)

3000

1300

20xF1K5

14

1500

1511

1900 (1 per phs)
650 (3 per phs)

3300

1900 (1 per phs)
650 (3 per phs)

4500

170M6466

4500

1900

1300

1310

1700 (1 per phs)
575 (3 per phs)

2900

1700 (1 per phs)
575 (3 per phs)

3900

170M6466

3900

1700

20xF1K9

(2)

14

1800

1914

2400 (1 per phs)
800 (3 per phs)

4200

2400 (1 per phs)
800 (3 per phs)

5700

170M6466

5700

2400

1500

1511

1900 (1 per phs)
650 (3 per phs)

3200

1900 (1 per phs)
650 (3 per phs)

4500

170M6466

4500

1900

20xF2K2

(2)

14

2000

2267

2900 (1 per phs)
950 (3 per phs)

5000

2900 (1 per phs)
950 (3 per phs)

6700

170M6466

6700

2900

1800

1914

2400 (1 per phs)
800 (3 per phs)

4200

2400 (1 per phs)
800 (3 per phs)

5700

170M6466

5700

2400

(1)

20DF820 drives (ND) are only capable of producing 95% of starting torque under 10 Hz.

(2)

Not available with 700S Control.

(3)

Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.

(4)

Maximum protection device size is the highest rated device that supplies drive protection.

(5)

These fuses and disconnect are supplied with AC input NEMA/UL Type 1 drives.

(6)

Inverse time breaker. Ratings shown are maximum.

(7)

Maximum allowable rating by US NEC. Exact size must be chosen for each installation.

(8)

Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.