PowerFlex 700S and 700H Frames 10...14 IP00, NEMA/UL Open Power Structures

700S Control Connections

1. To access the ASIC board(s), remove the front protective cover(s) from

the power structure(s) as shown below.

2. Connect the 24V power supply cable and the fiber optic cables between

the Voltage Feedback Board and the Common Mode Filter and Fiber
Optic Interface or Fiber Optic Star Interface boards. Refer to

Table 22

below for cable designations and connection points and figures

28

,

29

,

30

and

31

for connector locations.

Complete fiber optic cable connections after all electrical wiring has

been completed to avoid damage to the cables.

Ensure that the fiber optic cables do not contact sharp objects that can

cause damage to the cables.

The fiber optic cables have a minimum bending radius of 50 mm (2.0

in.).

Table 22 - Voltage Feedback Board Cable Designations

IMPORTANT

Verify correct cable/connector placement. Connecting the wires incorrectly
could damage components.

Connect this Point …

to this Point …

Location

Connector

Location

Connector

Voltage Feedback Board

J8

Common Mode Filter Board

J5

J5

Fiber Optic Interface or Fiber
Optic Star Interface Board

J7

J4

J6

Frames 13 and 14

Frames 10…12

(Frame 10 shown)