Tcb-pcnt20e – Toshiba RAV-SM560A User Manual

Page 101

Advertising
background image

177

Setup of the Address No.

To connect the indoor unit to the central remote controller using the adapter, it is necessary to set up the network address No.

• It is required to agree the network address No. with the central remote controller system No.

• The network address No. is set to 1 at the shipment from the factory.

The following two methods are used for setup.

1. Setup from the remote controller at the indoor unit side

• This method is available only when [7] of the setup switch SW01 on the adapter P.C. board is OFF.

<Procedure> Set up the address No. while the air conditioner stops.

1

Push

and

buttons for 4 seconds or more.

In case of the group control, the unit No.

ALL

is displayed, and then all the indoor units in the group control are selected.

(Fig. 1)

In this time, the fans of all the selected indoor units start and the swing operation also starts in the models with flaps.

(Keep the display status of

ALL

without pushing

UNIT

button.)

In case of individual remote controller with no group control, the system address and the indoor unit address are displayed.

(Fig. 1)

Setup data

0001
0002
0003



0064

0099

Network address No.

1
2
3



64

No setting (Shipment from the factory.)

UNIT

UNIT No.

CODE No.

SET DATA

R.C.

No.

SET

CL

1
5

2

3

4

2

Using

/

buttons, specify the item code

03

.

3

Using

buttons, select the setup data.

The following table shows the setup data. (Table 1)

4

Push

SET

button.

(When the display goes on, the setup data is accepted.)

To change the setup item, return to the step

2

.

5

Push

button. The status returns to the normal stop status.

(Table 1)

2. Setup by the switch on the adapter P.C. board

When the remote controller is not found, or when you do not want to change the setup of network address No. on the remote
controller, set up the address No. by using the setup switch SW01 (Network address No. setup switch) on the adapter P.C.
board.

<Procedure>

1

Turn off the power supply.

2

Set [7] of the address No. setup switch
SW01 to ON side.
Accordingly, the setup of the address No. from
the remote controller is invalidated. (Fig. 2)

3

The network address No. is set up by com-
bining ON/OFF of the address No. setup
switch, from SW01 [6] to [1].
For the relation between ON/OFF combination
and the address No., see (Table 2).
A case when the address No. is set to 16 is
shown in (Fig. 3).

When the network address No. has been changed, turn on the power of the central remote controller again or reset the
central remote controller from the reset hole on the control panel of the central remote controller.

SW01

ON side

OFF side
(Numeral side)

1

2

3

4

5

6

7

Address No. setup on the remote controller is invalid.

Address No. setup

Setup example (Address No. 16)

ON side

OFF side
(Numeral side)

1

2

3

4

5

6

7

(Fig. 2)

(Fig. 3)

Address No.

01

02

03

04

05

06

07

08

09

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

Address No.

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

51

52

53

54

55

56

57

58

59

60

61

62

63

64

Address No. setup table (SW01)

(Table 2)

: ON side, : OFF side

Requirement in Service Time

When using this product as the service part for change of the adapter P.C. board, be sure to set the setup switch SW01
(Network address No. setup switch) on the adapter P.C. board so that it is same as one before change.

TCB-PCNT20E