183

Concealed Duct type

Deodorant Filter, Ammonium Filter

Installation Manual

Deodorant Filter

Model: TCB-DF11BE

TCB-DF21BE
TCB-DF31BE
TCB-DF41BE

Ammonium Filter

Model: TCB-DF11BE-AM

TCB-DF21BE-AM
TCB-DF31BE-AM
TCB-DF41BE-AM

NOTES

• Do not unpack the filter until you

use it. (Otherwise, life of the
deodorant filter or ammonium filter
is shortened.)

• Keep this Manual with Owner’s

Manual of the indoor unit.

Safety Cautions

• Before installation work, read thoroughly this “Safety Cautions” to install the air conditioner correctly.

• This “Safety Cautions” describes the important contents concerned to the safety. Be sure to keep in mind these items.

Symbols and meanings are as described below.

WARNING

CAUTION

Indicates “User may be dead or seriously injured (*1) if it is incorrectly used.”

Indicates “It is assumed that user may be injured (*2) or property damage (*3) may occur if it is
incorrectly used.”

*1: “Serious injury” means a disease which has an after-effect or requires hospitalization or long-term going to the hospital for

treatment, such as loss of sight, burn (by high temperature or low temperature), electric shock, fracture, poisoning, etc.

*2: “Injury” means hurt, burn, electric shock, etc. which does not require hospitalization or long-term going to the hospital for

treatment.

*3: “Property damage” means enlarged damage concerned to house, household effects, domestic animal, pet, etc.

Explanation of picture symbols

indicates prohibition (prohibited action).

The concrete prohibited action is indicated with picture or sentence in or near the picture symbol.

indicates that the forced instructed action (Act necessarily).

The concrete instructed action is indicated with picture or sentence in or near the picture symbol.

indicates an item with care.

The concrete item to be cautioned is indicated with picture or sentence in or near the picture symbol.

WARNING

• Do not put a plastic bag including filter on a place where

hands of a small child can reach.
If the child puts the bag on his head, it may seal
his mouth or nose resulting in choke of death.

CAUTION

• Install the suction grille surely to the main unit.

If an incomplete installation is performed,
falling of the suction grille causes an injury.

Specifications

Deodorant filter
model name

Conformed air
conditioner model name

Quantity

Initial deodorant
performance

Deodorant durable
performance

TCB-

TCB-

TCB-

TCB-

DF11BE

DF21BE

DF31BE

DF41BE

1101BT

561BT

801BT

to

1401BT

1

1

2

2

85%

Approx. 9 months

Ammonium filter
model name

Conformed air
conditioner model name

Quantity

Initial deodorant
performance

Deodorant durable
performance

TCB-

TCB-

TCB-

TCB-

UFH11BE-AM UFH21BE-AM UFH31BE-AM UFH41BE-AM

1101BT

561BT

801BT

to

1401BT

1

1

2

2

95%

Approx. 15 months

Air filter

Filter sold separately

• Deodorant filter
• Ammonium filter

Filter sold
separately

Hook

Indoor unit

Short plug position (CN112, CN111, CN110 from the left)

Short plug position

External

static

pressure

40Pa

Standard
(At shipment)

70Pa

High static-
pressure 1

100Pa

High static-
pressure 2

20Pa

Low static-
pressure

Filter sold separately

Standard filter
(At shipment)

Zeolite-3G deodrant filter

*1
High-efficiency filter 65
High-efficiency filter 90
Deodorant filter
Ammonium filter

——

——

Short

CN112 CN111 CN110

Open

CN112 CN111 CN110

CN112 CN111 CN110

CN112 CN111 CN110

UNIT

SET

CL

SETTING

UNIT No.

CODE No.

SET DATA

R.C.

No.

1

4

6

2
3

5

Installation of filter sold separately

1

Remove the air filter, and install a filter sold separately to the
suction port.
Push the filter sold separately completely up to the end.
Check that the rear side is hanged to the hook.

2

Install the air filter
Be sure to fix the air filter with clamps in order to prevent falling.
(Clamps are attached to the indoor unit.)

NOTE

These filter cannot be reused even if it is washed.

Maintenance of filter sold separately

• Clean the filter sold separately once per 2 months.

1

Take out the filter sold separately in the reverse order of
“Installation of filter sold separately”.

2

Sweep away the dust of the filter sold separately with a cleaner.

3

Install the filter sold separately.

To install a filter sold separately, be sure to set the
fan referring the following description.
* The filter sold separately cannot be installed to an

air conditioner built in with auxiliary electric heater.

Setup of fan when building in the filter sold separately:

Necessary at initial installation only

Two methods are provided for setup, one is to use a wired remote controller sold separately
and the other is to exchange the short plug on the indoor microcomputer P.C. board.

[Using a wired remote controller sold separately]

(Procedure) Perform the setup while the equipment stops.

1

Push

SET

+

CL

+

buttons concurrently for 4 seconds or more.

The firstly displayed unit No. is the master indoor unit address of the group control.
In this time, the fan of the selected indoor unit only operates.

2

Every pushing

UNIT

button, No. of the group control units are displayed in

order.
In this time, the fan of the selected indoor unit only operates.

3

Using set temperature

and

buttons, specify the item code “5d”.

4

Using timer time

and

buttons, select from the set data.

For contents of the setup data, refer to the table at the right.

5

Push

SET

button.

(When flashing display changes to lighting display, the setup completes.)

6

Pushing

button returns the state to the normal stop state.

* Setup can be performed only by the

wired remote controller. If setup is not
performed, air volume is decreased and
dewing occurs.

• Item code 5d

Set data

0000

0001

Filter sold separately

Standard filter (At shipment)

High-efficiency filter (65%)
(TCB-UFM11BE to UFM41BE)
High-efficiency filter (90%)
(TCB-UFH51BE to UFH81BE)

[Exchange of short plug on indoor microcomputer P.C. board]

To exchange the static pressure, there is a method other than the
abovementioned method by wired remote controller, which is to shift the
short plug on the indoor microcomputer P.C. board as shown in the
following table. Adopt this method in case of using a wireless remote
controller, etc.
* However, after exchanging once, be careful to shift the short plug to the

standard position (At shipment) in order to return to the standard setup
(follow to E

2

PROM setup) though the setup for high static-pressure 1,

high static-pressure 2, or low static-pressure can be arbitrarily performed.
It is necessary to rewrite data from the wired remote controller sold
separately in the set data “0000”.

• Select with shifting of the short plug on the indoor unit

microcomputer P.C. board.

*1 Resistance of high-

efficiency filter 65 and
90, deodorant filter, or
ammonium filter is
equivalent to 30Pa.
Therefore, set the
resistance (external
static pressure) of a duct
to be connected to 40Pa.

DEBF-E

TCB-DF11, 21, 31, 41BE

TCB-DF11, 21, 31, 41BE-AM

Advertising