Installation of indoor unit, Restriction to installation – Toshiba RAV-SM560A User Manual

Page 26

Advertising
background image

– 102 –

RAV-SM560, 561, 800, 801BT-E
RAV-SM1101, 1401BT-E

Concealed duct type

Ledge ceiling concealed duct type

NOTE:

• Opening area of the return grille should be larger than

the one for suction port (Air filter) of the indoor unit.

Channel

Supply chamber

Supply grille

Supplying

Supplying

Returning

Return air grille

Indoor unit

200mm (diam.)
round duct

Supply grille

Supplying

Supplying

Indoor unit

200mm (diam.)
round duct

Supply
chamber

Returning

Return air grille

NOTE:

• Recommended supplying grille size 400 cm² each or more

Quality of supplying grilles

SM561BT

SM801BT

SM1101BT

SM1401BT

2

3

4

4

Restriction to installation

1. Installation clearance

• As shown in the figure, keep clearance around the indoor unit.

100mm

or more

300mm

or more

100mm

or more

Inner ceiling
100mm or more

3

INSTALLATION OF INDOOR UNIT