171

Tightening connection

CAUTION

• Do not apply excessive torque. Otherwise, the

nut may crack depending on the conditions.

(Unit : N•m)

• Tightening torque of flare pipe connections

Pressure of R410A is higher than that of R22.
(Approx. 1.6 times) Therefore, using a torque
wrench, tighten the flare pipe connecting sections
which connect the indoor and outdoor units of the
specified tightening torque.

Incorrect connections may cause not only a gas
leak, but also a trouble of the refrigeration cycle.

Align the centers of the connecting pipes and tighten
the flare nut as far as possible with your fingers.

Then tighten the nut with a spanner and torque wrench
as shown in the figure.

Thermal insulating process

Apply thermal insulation to pipes at liquid and gas
sides separately.

• Be sure to use thermal insulator with heat resisting

temperature 120˚C or more for pipes at gas side.

• Using thermal insulators attached to the indoor unit

and Elbow piping kit, apply thermal insulating
process surely to pipe connecting section without
clearance.

CAUTION

Apply thermal insulating process surely so
that no exposure cannot be found up to the
end of the pipe connecting section of the
indoor unit. (If a part of the pipe is exposed,
leakage may be caused.)

Outer diam. of copper pipe

6.4 mm (diam.)

9.5 mm (diam.)

12.7 mm (diam.)

15.9 mm (diam.)

Tightening torque

14 to 18 (1.4 to 1.8 kgf•m)

33 to 42 (3.3 to 4.2 kgf•m)

50 to 62 (5.0 to 6.2 kgf•m)

68 to 82 (6.8 to 8.2 kgf•m)

Flare at

indoor

unit side

Flare at

outdoor

unit side

Half union

Flare nut

Externally
threaded side

Internally
threaded side

Use a wrench to secure.

Use a torque wrench to tighten.

For the connection of refrigerant pipe and thermal
insulating process after hanging down the indoor
unit, refer to the Installation Manual attached to the
indoor unit.

Fix with vinyl tape.

Set the notch upward.

Attached thermal insulating pipe

Elbow piping kit side

How to install drain up kit

1. Mount the drain up kit fixture to the rear side inside

of the indoor unit. (1 screw)

2. Hang the temporary hanging hook of the drain up

kit to the side slit of the indoor unit from inner side.

Screw the drain up kit to the indoor unit.

(3 screws: Ceiling surface, side face, and drain up
kit fixture)

Screwing of drain up kit fixture

Drain up kit fixture

Side slit of indoor unit

Temporary hanging
hook of drain up kit

Drain up kit

Drain up kit

Hang temporary
hanging hook from
inside of indoor unit.

Screwing
(To side face)

Screwing
(To Drain up kit fixture)

Screwing (To Ceiling surface)

3

INSTALLATION PROCEDURE OF DRAIN-UP KIT