Drain piping work – Toshiba RAV-SM560A User Manual

Page 32

Advertising
background image

– 108 –

RAV-SM560, 561, 800, 801BT-E
RAV-SM1101, 1401BT-E

5

DRAIN PIPING WORK

Piping material

• For laying pipes underground, use hard vinyl

chloride pipe. VP25 (Inner diamater Ø32mm)

Piping and cautions

• Set drain side of pipe at downward slope.

(1/100 or more)

• Be sure to apply thermal insulation (foaming

polyethylene, 10mm-thickness or more) for pipes
passing through the room.

• Adhere the connecting sections with vinyl chloride

agent surely so that no water leakage is caused.

• Apply adhesive agent without unevenness around

the portion approx. 40mm from the end of hard
polyvinyl-chloride pipe.

• Push the vinyl pipe in the drain socket completely

up to the end of the socket.

• Do not apply strength to the connecting part until

the adhesive agent has dried and hardened.

• Support the piping with hanging bracket so that the

force is not applied to connection sections of pipe
and pipe is not waved.

NOTES :

• Do not make slack or trap at halfway across piping.

• Set pipes so that the end of drain pipe is not dipped in

water, and also keep space 50mm or more to the
ground.

• After piping work, check if water drains smoothly.

• Hole should be made at a slight downward slant to

the outdoor side.

• When connecting extension drain hose, insulate the

connecting part of extension drain hose with shield
pipe.

Thermal-insulating process

• After checking water drain, be sure to apply the

thermal-insulating for connecting portion of the
pipes.

• Apply taping so that there is no clearance on the

fitting part of thermal-insulator of the main unit with
the insulator procured locally.

Trap

Arched shape

Support
bracket

1/100 or more
downward slope

Thermal
insulator

Indoor
unit

1.5m to 2m

50 mm
or more

Do not put the drain hose
end into water or drainage.

• As shown in the figure, set the collective piping such

as the ceiling duct so that waste water does not back
up from the main pipe.

Fit insulator so that
there is no clearance.

Hard polyethylene vinyl pipe
(Procured locally)

Thermal insulator
(Procured locally)

Fix thermal insulator
by taping

Thermal insulator
(Main unit side)

Advertising