RAV-SP1100, 1400AT-E
RAV-SM1100, 1400AT-E

3

SELECTION OF INSTALLATION

Before installation

Be careful to the following items before installation.

Length of refrigerant pipe

<SM1100AT-E, SM1400AT-E>

* Caution at addition of refrigerant

When the total length of refrigerant pipe exceeds
20m, add 40g/m of refrigerant and the maximum total
length of pipe is 50m.
(Max. amount of additional refrigerant is 1200g.)

Charge the refrigerant accurately. Overcharge may
cause a serious trouble of compressor.

Length of refrigerant pipe

connected to

indoor/outdoor unit

20m or shorter

*

21m to 50m

Item

Addition of refrigerant is
unnecessary at the local site.

<Addition of refrigerant>
Add 40g of refrigerant for every
1m of pipe which exceeds 20m.

CAUTION

<SP1100AT-E, SP1400AT-E only>

When using an air conditioner under low outside temperature condition (Outside temp.:–5°C or lower) with
COOL mode, prepare a duct or wind shield so that it is not affected by the wind.

<Example>

<SP1100AT-E, SP1400AT-E>

Length of refrigerant pipe

connected to

indoor/outdoor unit

30m or shorter

*

31m to 70m

Item

Addition of refrigerant is
unnecessary at the local site.

<Addition of refrigerant>
Add 40g of refrigerant for every
1m of pipe which exceeds 30m.

* Caution at addition of refrigerant

When the total length of refrigerant pipe exceeds
30m, add 40g/m of refrigerant and the maximum total
length of pipe is 70m.
(Max. amount of additional refrigerant is 1600g.)

Charge the refrigerant accurately. Overcharge may
cause a serious trouble of compressor.

Air purge

• For air purge, use a vacuum pump.

• Do not use refrigerant charged in the outdoor unit for

air purge. (The refrigerant for air purge is not con-
tained in the outdoor unit.)

Electrical cabling

• Be sure to fix the power cables and indoor/outdoor

connecting cables with clamps so that they do not
contact with the cabinet, etc.

Suction hood (Rear side)

Suction

Suction

Suction hood (Side)
Discharge hood

Fin

Fin

Discharge upward/downward
or leftward is also available.

Use it at location
where a side wind
drives thickly

( )

Discharge