Rbc-ax22ce – Toshiba RAV-SM560A User Manual

Page 88

Advertising
background image

164

Test run

Before test run

• Before turning on the power supply, carry out the following procedure.

1) Using 500V-megger, check 1MW or more exists between the terminal block 1 to 3 and the earth.

If 1MW or less is detected, do not run the unit. Do not apply to the remote controller circuit.

2) Check the valve of the outdoor unit being opened fully.

• To protect the compressor at activation time, leave power-ON for 12 hours or more be for operating.

How to execute a test run

Using the remote controller, operate the unit as usual.
For the procedure of the operation, refer to the attached Owner’s Manual.
A forced test run can be executed in the following procedure if the operation stops by thermo.-OFF.
In order to prevent a serial operation, the forced test run is released after 60 minutes have passed
and returns to the usual operation.

CAUTION

When the remote controller is used for the first time, it accepts an operation approx. 5 minutes
after the power supply has been turned on.
It is not a trouble, but is because the setup of the remote controller is being checked.
For the second power-ON time and after, approx. 1 minute is required to start the operation by the
remote controller.

NOTE

Do not use the forced test run for cases
other than the test run because it applies
an excessive load to the devices.

In case of wireless remote controller

Procedure

Operation contents

Turn on power of the set.

After installation, the operation is not accepted for 5 minutes when the power has been turned on
at the first time, and 1 minute when the power has been turned on at the second time and after.
Perform a test run after a specified time has passed.

Push [

] button on the remote controller, change the operation mode to [ ] or [

] by using [

]

button, and then change the air speed to [

] by [ ] button.

Cooling test run

Set temperature to [18˚C] by using [ ] button.

Push [ ] button to set temperature to [19˚C] just
after confirming the receiving sound “Pi”.

Push [ ] button to set temperature to [18˚C] just
after confirming the receiving sound “Pi”.

Heating test run

Set temperature to [30˚C] by using [ ] button.

Push [ ] button to set temperature to [29˚C] just
after confirming the receiving sound “Pi”.

Push [ ] button to set temperature to [30˚C] just
after confirming the receiving sound “Pi”.

Repeat the procedure

4

5

4

5

. After approx. 10 seconds, all the display lamps [

]

(Green), [

] (Green), and [

] (Yellow) of the wireless sensors flash, and the operation starts.

If the lamps do not flash, repeat the procedure

2

and after.

When the test run has finished, push [

] button to stop the operation.

<Outline of test run by using a wireless remote controller>

Cooling test run : Start/Stop 18˚C

19˚C

18˚C

19˚C

18˚C

19˚C

18˚C

(Test run)

Start/Stop

Heating test run : Start/Stop 30˚C

29˚C

30˚C

29˚C

30˚C

29˚C

30˚C

(Test run)

Start/Stop

1

2

3

4

5

6

7

ADR

Be sure to set the
air speed to [ ].

2

3, 4, 5, 6

2, 7

How to set up filter sold separately of the high ceiling

• When the height of ceiling to be installed with a filter exceeds

3.5m or when installing a filter sold separately, tap-up of DC fan
is required. Tap-up of DC fan can be set at No.2 (Tap 1) and No.4
(Tap 2) of DIP switch [S003] on the wireless sensor P.C. board.
The wireless sensor P.C. board appears by removing screws at
the rear side of the wireless sensor unit and the rear cover.

Setup for high ceiling

[NOTE]
If the setup has been once performed, the set
contents of Type 1, 3, and 6 can be arbitrarily
changed. However, it is required to turn off [S003]
No.2 (Tap 1) and No.4 (Tap 2) of DIP switch and
also required to rewrite by the wired remote
controller sold separately to return the set content
to the standard one (at shipment). (For rewriting by
a wired remote controller sold separately, refer to
the Installation Manual attached to the indoor unit.)

Never set ON to DIP switch [S003] No.1 (Test
run). (A test run is carried out on the remote
controller.) (For the test run, refer to the
Installation Manual attached to the indoor unit.)

[S003] No.2 (Tap 1) and
[S003] No.4 (Tap 2) are used.

Setup for filter sold separately

Standard (At shipment)

Type 1

[S003] No.2

(Tap 1)

OFF

OFF

[S003] No.4

(Tap 2)

OFF

ON

Installable

height of ceiling

3.5m

4.0m

Standard (At shipment)

Type 1

Type 3

Type 6

[S003] No.2 (Tap 1)

OFF

OFF

ON

ON

[S003] No.4 (Tap 2)

OFF

ON

OFF

ON

Filter sold separately

Standard filter

Optical regeneration deodorant filter

High-performance filter

Deodorant filter / Ammonia deodorant filter

How to handle the remote controller

• In case using remote controller mounting

to the wall, etc.

Check a signal is received correctly by

pushing

button at the position to be fixed.

• Replacement of battery
1. Holding the both ends of the cover and

remove it by sliding downward.

2. Correctly insert 2 AAA alkali batteries

matching + and - polarities with indica-
tions.

3. Push SET button with something tipped

and attach the cover.

Cautions for installation of the remote controller

• To operate the remote controller by fixing it to the wall,

etc. with a remote controller holder, turn on the fluores-
cent lamp, operate the remote controller at the position to
be fixed, check the air conditioner normally operates, and
then mount it.

• When the room temperature is sensed by the remote

controller, mount the remote controller paying attention to
the following items.

• Place not exposed directly to cold or hot wind.
• Place not exposed directly to the sunlight.
• Other places where the remote controller is not

influenced.

Explanation to customers

• Hand over the “Owner’s Manual” and “Installation

Manuals” to the customer after installation works.

• Explain usage and maintenance of the remote controller

according to “Owner’s Manual”.

ON

12

3

4

2

3

4

1

2

Mounting screw
Truss tapping
4 x 16

• To take off

remote controller,
pull it toward you.

Put on.

Push.

RESET button

Cover

RBC-AX22CE

Advertising