1. Remove a screw and then remove cover of the

electric parts box.

2. Strip wire ends (10 mm).

3. Match wire colors with terminal numbers on indoor

and outdoor units’ terminal blocks and firmly screw
wires to the corresponding terminals.

4. Connect the ground wires to the corresponding

terminals.

5. Fix the cable with cord clamp.

6. Fix cover of the parts box and the terminal block

surely with the fixing screws.

Make a loop on the cable for margin of the length
so that the electric parts box can be taken out
during servicing.

Terminal block
for remote controller
cabling of indoor unit

A
B

Approx. 200mm

W : White
B : Black

W

B

Remote controller cable
(Local procure)

Remote controller unit or
cable from sensor part

Connecting
part

Remote
controller unit
or sensor part

Remote Controller Cabling

• Strip off approx. 14mm the cable to be connected.

• Non polarity, 2 core cable is used for cabling of the

remote controller.

• Twist cable of the remote controller to be connected

with cable of the remote controller unit (or sensor),
and press-fit them with a wire joint.
Wire joints (White: 2 pieces) are included in the
attachments to the remote controller (sold
separately) or the wireless remote controller kit (sold
separately).

Cabling diagram

Cable from remote
controller unit

Remote controller cabling

Wire
joint

Wiring diagram

• For details of cabling/installation of the remote

controller, refer to the Installation Manual attached to
in the remote controller.

A

B

1

1

L

N

2

2

3

3

Remote controller

Remote controller
cable

Indoor side

Outdoor side

(Single phase 220-240V)

Indoor/Outdoor
connecting cable

Connecting cable

Earth line

10

10

120

50

2 3

1

60 70

A

B

C

Advertising