Example Configuration

To configure Analog IN 1 for a specific sample rate, report rate, and switch power output voltage, follow these steps.

For this specific configuration example, we will be using a DX80N9X2S-P1 SureCross Performance Node. Configuring other Node mod-
els is the same, except that the input point associated with Analog IN 1 may be different.

1. To use the UCT to configure your Node, first set the Node's DIP switch to be Host Configured. This overrides all other DIP switch

settings and relies on the host system or UCT to configure the device. Consult your Node's datasheet to determine which DIP
switch selected between Host Configured (ignores DIP switches) and DIP switch configuration.

2. Determine which analog input you are configuring. For this example, we are configuring Analog IN 1 of a -P1 Node. This is input 3.

Configuring the Switch Power Output

To configure the switch power, you must set the power supply, switch power voltage, and warm-up parameters. These parameters must
be assigned to the same I/O point as the analog input you are configuring, in this example this is I/O point 3 (Analog IN 1). After configur-
ing each parameter, click the Send button to send the configuration changes to the Gateway's configuration file.

1. Set the power supply parameter. In this example, we are associating SP1 with Analog IN 1 (I/O point 3 on the -P1 Performance

Node).

2. Click on the Send button to send this setting to the Gateway's configuration file.
3. Set the switch power voltage parameter. In the example screen shot show below, we are setting the switch power voltage to 15V

and the switch power voltage is associated with I/O point 3 (Analog IN 1 for the -P1 Performance Node).

4. Click on the Send button to send this setting to the Gateway's configuration file.
5. Set the warm-up parameter. In this example, we are setting the switch power warm-up time to one (1) 62.5 millisecond interval, or

62.5 milliseconds.

SureCross User Configuration Tool (UCT)