Power Connection Guidelines for DC-Powered Routers

When the Cisco XR 12404 Router operates with a DC PDU, observe these
guidelines:

A Cisco XR 12404 Router configured with a DC PDU and DC-input PEMs has
a maximum power rating of 35A per power module and requires a dedicated DC
power source to support this maximum current. The facility DC source circuit
breaker protection needs to comply with safety local codes and regulations.
This circuit breaker protects against short-circuit and overcurrent faults in
accordance with United States National Electrical Code NFPA 70 (United
States), Canadian Electrical Code, part I, CSA C22.1 (Canada), and IEC 364
(other countries).

DC power cable leads should be #6 American Wiring Gauge (AWG)
high-strand-count wire.

Provide a dedicated power source for each power entry module installed in
the router.

66969

North American plug

L6-20 20A

(for 240V units)

Australian plug

AS 3112 10A

European plug

CEE 7/7 16A

Italian plug

CEI 23-16/VII 10A

United Kingdom plug

BS 1363 13A

North American plug

5-15 15A