Chapter 4 Troubleshooting the Installation
Troubleshooting the Cooling Subsystem
4-26
Cisco XR 12404 Router Installation Guide
OL-13830-02
clearance (at least 6 inches, 15.24 cm) around all sides of the chassis to allow 
cooling air to enter and hot air to exhaust. Should an overtemperature 
condition occur at initial startup:
–
Check the condition of the air filter. If the air filter appears dirty, you 
should remove the air filter and replace it; or remove the air filter, take it 
away from the chassis, and vacuum the air filter.
–
The overtemperature condition message could also indicate a faulty 
component or temperature sensor. Before the system shuts down, use the 
show environment all or show environment table commands to view 
the internal system environment including voltages and temperatures 
measured at each card.
If you are still unable to resolve the problem, contact a service representative for 
assistance.