05 input wiring specifications – Tweco A80-A120 CutMaster User Manual

Page 17

Advertising
background image

CUTMASTER A80, A120

Manual 0-5119

INTRODUCTION

2-3

Power Supply Dimensions & Weight

Ventilation Clearance Requirements

26.3"

0.668 m

63 lb / 28.6 kg

10"

254 mm

13.78"

350 mm

Art # A-08459

6"

150 mm

24"

610 mm

6"

150 mm

6"

150 mm

Art # A-07925_AB

2.05 Input Wiring Specifications

CutMaster A80 Power Supply Input Cable Wiring Requirements

Input voltage

Freq

Power Input

Suggested Sizes

Volts

Hz

kVA

I

1

max

I

1

eff

Fuse (amps)

Flexible Cord

(mm

2

)

Flexible Cord

(AWG)

3 Phase

380

50

18.4

28

25

35

10

8

400

50

18.7

27

24

35

10

8

Line Voltages with Suggested Circuit Protection and Wire Sizes

Based on National Electric Code and Canadian Electric Code

CutMaster A120 Power Supply Input Cable Wiring Requirements

Input voltage

Freq

Power Input

Suggested Sizes

Volts

Hz

kVA

I

1

max

I

1

eff

Fuse (amps)

Flexible Cord

(mm

2

)

Flexible Cord

(AWG)

3 Phase

380

60

23

35

32

35

6

10

400

50

23.6

34

31

35

6

10

Line Voltages with Suggested Circuit Protection and Wire Sizes

Based on National Electric Code and Canadian Electric Code

NOTE

Refer to Local and National Codes or local authority having jurisdiction for proper wiring requirements.
The suggested sizes are based on flexible power cable with power plug installations. For hard-wired installations

refer to local or national codes.
I1max is taken at TDC rated minimum duty cycle.
I1eff is taken at TDC 100% rated duty cycle