Arcmaster 401mst power source – Tweco ArcMaster 401MST User Manual

Page 32

Advertising
background image

ARCMASTER 401MST POWER SOURCE

INSTALLATION, OPERATION AND SETUP

3-2

Manual 0-5287

WARNING

ELECTRIC SHOCK can kill; SIGNIFICANT DC VOLTAGE is present after removal of input power.

DO NOT TOUCH live electrical parts.
SHUT DOWN welding power source, disconnect input power employing lockout/tagging procedures. Lockout/

tagging procedures consist of padlocking line disconnect switch in open position, removing fuses from fuse box,

or shutting off and red-tagging circuit breaker or other disconnecting device.
Electrical Input Requirements
Operate the welding power source from a single or three-phase 50/60 Hz, AC power supply. The input voltage

must match one of the electrical input voltages shown on the input data label on the unit nameplate. Contact the

local electric utility for information about the type of electrical service available, how proper connections should

be made, and inspection required. The line disconnect switch provides a safe and convenient means to completely

remove all electrical power from the welding power supply whenever necessary to inspect or service the unit.

NOTE

This unit is equipped with a three-conductor with earth power cable that is connected at the welding

power source end for single or three-phase electrical input power.

Do not connect an input (WHITE, BLACK or RED) conductor to the ground terminal.
Do not connect the ground (GREEN) conductor to an input line terminal.
Refer to Figure 3-1 and:

1. Connect end of ground (GREEN) conductor to a suitable ground. Use a grounding method that complies

with all applicable electrical codes.

2. For 3- phase operation, connect ends of line 1 (BLACK) and line 2 (WHITE) and line 3 (RED) input conductors

to a de-energized line disconnect switch.

For 1- phase operation, connect BLACK and WHITE input conductors. Insulate the RED Conductor.
3. Use Table 3-1 as a guide to select line fuses for the disconnect switch.

Fuse Size

Input Voltage

1 Phase

3 Phase

208 VAC

100 Amps

60 Amps

230 VAC

80 Amps

50 Amps

460 VAC

50 Amps

30 Amps

Table 3-1 Electrical Input Connections

NOTE

Fuse size is based on not more than 200 percent of the rated input amperage of the welding power

source (Based on Article 630, National Electrical Code).