31 ssg glazing, Figure 30 – Oldcastle BuildingEnvelope Reliance-TC User Manual

Page 31

Advertising
background image

GLAZING

R E L I A N C E - T C C U R T A I N W A L L I N S T A L L A T I O N M A N U A L

TM

2 1/2"

SSG vertical

Quarter points

Quarter points

1/4" splice joint

1/2"

face cover

splice joint

1

1
8

"

Face cover
(dashed)

FS-325

Pressure

Plate Splice

Face Cover

Splice

FIGURE 30

Pressure Plate / Face Cover Splicing & Sealing at SSG Mullions

(Intermediate Horizontal Shown; Head & Sill Similar)

3.21 After removing horizontal temporary retainers, locate pressure plates and face covers to run

continuous over SSG mullions. Pressure plate and face covers are not to exceed 3 lites in length.
Splice pressure plate and face covers at SSG mullion center line per

FIGURE 30.

SEALING NOTES:

1. Prior to attaching face covers, seal between

pressure plates.

2. Attach face covers and seal joint (a foam

backer rod can be used to aid in sealing)

Butt-spice isolator

as required (seal joint)

1/2"

face cover

splice joint

Backer rod between

face cover and

pressure plate

Pressure bar
(dashed)

Face cover

Weep holes

Attachment holes

MAY 2013

31