40 entrances, Thermal entrance frames – Oldcastle BuildingEnvelope Reliance-TC User Manual

Page 40

Advertising
background image

3

7/

16"

3 7/16"

3/4

"

FS-325
#12-24 X 1 1/2"
DrillFlex

AD-450
Subframe

AD-403
Door stop

WW-122

WW-122

FIGURE 42

Attaching Thermal

Door Subframe

THERMAL ENTRANCE FRAMES

C.3 THERMAL SUBFRAME INSTALLATION:

C.3.1 Attach AD-204 threhsold clip to bottom of each subframe jamb with two (2) FS-22 #10 x 1/2" Flat

Head Screws

C.3.2 Install WW-122 filler into verticals and horizontal, attach w/ FS-325 @ 18" o.c. Bed fillers in sealant

and cap seal fasteners at all fillers.

C.3.3 Bed subframes in sealant and anchor to curtain wall framing members with FS-325#12-24 x 1 1/2"

Drillflex at 18" on center. Seal joint between jamb and header subframes. Seal also tops of jamb subframe.

SEE FIGURE 42

.

C.3.4 Bed threshold in sealant, attaching TH-44 clips with FS-42 #12 x 1/2" Phillips Flat Head screws. Marry

threshold seal with subframe and main system seal.

C.3.5 Install door stops onto subframe with SC-1 clips and FS-15 rivets @ 18" O.C. Locate clips around the

subframe anchor screws. Vertical stops run through.

C.3.6 Install door per DOOR & FRAME INSTALLATION & GLAZING MANUAL

R E L I A N C E - T C C U R T A I N W A L L I N S T A L L A T I O N M A N U A L

TM

MAY 2013

40