Rice Lake 720i Programmable Indicator/Controller - Installation Manual User Manual
Page 81

ALWAYS
NEVER
BRANCH
0
1–32
G
Setpoints
75
Figure 8-8. ALWAYS and NEVER Setpoint Parameters
SETPTS Menu
Parameter
Choices
Description
Level 2 submenus
SETPT 1–
SETPT 32
OFF
GROSS
NET
–GROSS
–NET
ACCUM
ROC
+REL
–REL
%REL
RESREL
PAUSE
DELAY
WAITSS
COUNTER
AUTOJOG
COZ
INMOTON
INRANGE
BATCHPR
TIMER
CONCUR
TOD
DELTA
CHKWEI
ALWAYS
NEVER
Specifies the setpoint kind.
GROSS, NET, –GROSS, –NET, ACCUM, ROC, +REL, –REL, %REL, RESREL. and
TOD setpoint kinds can be used as either batch or continuous setpoints.
PAUSE, DELAY, WAITSS, COUNTER, AUTOJOG, DELTA, ALWAYS, and NEVER
setpoint kinds can only be used in batch sequences.
COZ, INMOTON, INRANGE, BATCHPR, TIMER, CONCUR, and CHKWEI setpoint
kinds can only be used as continuous setpoints.
See Table 8-1 on page 65 for more information about setpoint kinds.
BATCHNG
OFF
AUTO
MANUAL
Batching enable. Set to AUTO or MANUAL to allow a batch sequence to run.
MANUAL requires a BATSTRT digital input, BATSTART serial command, Batch Start
softkey, or the StartBatch function before the batch sequence can run. AUTO allows
batch sequences to repeat continuously.
Table 8-2. Setpoint Menu Parameters