Reading – KEYENCE DL-RS1A/IB User Manual

Page 11

Advertising
background image

9

Commands and Responses

Reading

External devices such as PLC's use the following communication commands to read data from
DL-RS1A.

„ Read from the specified sensor amplifier (SR command)

Command

Response

Error response

„ Read all data from all sensor amplifiers (M0 command)

Command

Response

Error response

„ Read output states and data from all sensor amplifiers (MS command)

Command

Response

Error response

S

R

CR LF

ID No.

Data No.

,

,

S

R

Data*

1

ID No.

Data No.

,

,

,

CR LF

E

R

,

S

R

Error No.

,

CR LF

M

0

CR LF

M

0

CR LF

Data of the sensor
amplifier with ID:00*

2

,

Data of the sensor
amplifier with ID:01*

2

……

,

Data of the sensor amplifier
with the last ID No.*

2

,

,

E

R

CR LF

,

M

0

,

Error No.

M

S

CR LF

M

S

Control
output*

3

Control
output*

3

Control
output*

3

CR LF

Data of the sensor
amplifier with ID:00*

2

,

,

,

,

Data of the sensor
amplifier with ID:01*

2

Data of the sensor
amplifier with the last ID No.*

2

,

,

Sensor amplifier with ID:00

Sensor amplifier with ID:01

Sensor amplifier with the last ID No.

E

R

CR LF

,

M

S

,

Error No.

Commands and Responses

„ Read with external input to the DRQ terminal (DRQ read)

You can send an input signal (by short-circuiting DRQ (terminal number 6) and SG (terminal number
1, 4, or 5)) from an external device such as a PLC instead of sending a command.

Response

Error response

*1

The data length is different depending on the data being read. (Up to 10 characters)

*2

Data length: 7 characters
When the measurement mode is displayed with %: ±***.** (Reading range: -999.99 to +999.99)
When the measurement mode is displayed with dimension: ±**.*** (Reading range: -99.999 to
+99.999)

*3

Data length: 2 characters
On the IB Series, the judgment output (HIGH/LOW/GO output) and the check output ON/OFF
are displayed with 2-digit number (ASCII characters). Convert the 2-digit number (ASCII
characters) read to a binary number and check the ON/OF status of each bit to check the
judgment output status.

• When the read data is "05":

"05" is converted to the binary number "0101".
When N.O.

Bit

Judgment output

When N.O.

When N.C.

0

0: HIGH judgment output OFF,

1: HIGH judgment output ON

0: HIGH judgment output ON,

1: HIGH judgment output OFF

1

0: LOW judgment output OFF,

1: LOW judgment output ON

0: LOW judgment output ON,

1: LOW judgment output OFF

2

0: GO judgment output OFF,

1: GO judgment output ON

0: GO judgment output ON,

1: GO judgment output OFF

3

0: Check output OFF,

1: Check output ON

0: Check output ON,

1: Check output OFF

2 ms min.

Input signal

ON

OFF

SG

RD

SD

SG

SG

DRQ

D

R

CR LF

Data of the sensor
amplifier with ID:00*

2

,

,

,

,

Data of the sensor
amplifier with ID:01*

2

Data of the sensor
amplifier with the last ID No.*

2

,

,

Sensor amplifier with ID:00

Sensor amplifier with ID:01

Sensor amplifier with the last ID No.

Control
output*

3

Control
output*

3

Control
output*

3

E

R

CR LF

,

D

R

,

Error No.

Reference

Bit 3: Check output OFF

Bit 0: HIGH judgment output ON

Bit 2: GO judgment output ON

Bit 1: LOW judgment output OFF