Press the arrow keys to access the options of the Weir Menu. Press Enter for your desired options. Once
completed, you will go to Step 9, Select Flow Type.

8. Nozzle—The only option here is Ken. Press ENTER.

Primary Element

Ken

Scroll through the Kennison Nozzle options with the arrow keys and press

ENTER.9.

Flow Type determines the units to use for measuring the flow rate. Select the Flow Type

by scrolling through the options with the arrow keys. Press ENTER.

Select Flow Type

* CFS

10. The Flow Format allows you to choose how many digits you want to the left and right of the decimal

point for displaying the flow rate. Scroll through the format options and press ENTER.

Pick Flow Format

* XXX.XX

Note: Weir: If you selected Other in the Menu, the controller asks you to enter a custom value for Crest Length.
Use the keypad to enter the Crest Length. Press the Enter Key. The display flashes a message acknowledging
your selection. Go to Step 9.

Note: CFS is cubic feet per second, GPS is gallons per second, GPM is gallons per minute, GPD is gallons per
day, and MGD is million gallons per day.

11. After selecting Flow Format, the display prompts you to select the Total Type, the units to use for

measuring total flow. The display shows:

Total Type

* CF

An asterisk indicates the default units. CF is cubic feet, GL is gallons, and MG is million gallons.

12. After selecting the Total Type, the display prompts you to select the Total Format or Totalizer Format.

This allows you to select how many digits you want to the left and right of the decimal point or how
many fixed zeros you want for displaying the total flow. The display shows:

Total Format

XXX000

13. Use the arrow keys to scroll through the options available. Press ENTER. The display shows:

Zero Calibration

Auto

The UltraWave Series controller has two methods of calibration, Auto and Manual, for a flow application.
For Auto calibration, you enter the maximum head and the current head. For Manual calibration, you
enter the maximum head and the zero distance. Press ENTER to select Auto or the arrow key to select
Manual, then ENTER. If you select Manual, skip Step 15 and go directly to Step 16 to calculate Zero
Distance.