AERCO BMK 6000 User Manual

Page 125

Advertising
background image

Benchmark 6000 Boiler Installation, Operation & Maintenance Manual

CHAPTER 8 – TROUBLESHOOTING GUIDE

OMM-0086_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 125 of 210

GF-133

Ph.: 800-526-0288

03/20/14

Figure 8-1: Gas Train Component and Pilot Gas Valve Location

Figure 8-2: Pilot Burner & Flame Detector Locations

SIGHT GLASS

MAIN FLAME
DETECTOR

TO PILOT
GAS LINE

BLOWER

BLOWER FLANGE

BURNER PLATE

PILOT
BURNER

PILOT FLAME

DETECTORS (2 EA.)

TO AIR/FUEL

VALVE

GAS

INLET

DOWNSTREAM LOW

GAS PRESSURE

SWITCH (6.9” W.C.)

HIGH GAS

PRESSURE

SWITCH

(10.5” W.C.)

MANUAL SHUT-OFF VALVE

UPSTREAM LOW GAS
PRESSURE SWITCH
(8.5” W.C.)

LEAK DETECTION BALL VALVE WITH 1/4" NPT PLUG

PILOT

REGULATOR

TEE WITH 1/4" PLUG
(INSTALL MANOMETER
HERE FOR PILOT
REGULATOR TESTS)

PILOT

SOLENOID

VALVE

PILOT GAS

VALVE

Advertising