Benchmark 6000 Boiler Installation, Operation & Maintenance Manual

CHAPTER 6 – SAFETY DEVICE TESTING

Page 88 of 210

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0086_0D

03/20/14

Ph.: 800-526-0288

GF-133

6.10 PURGE SWITCH OPEN DURING PURGE

The Purge Switch (and Ignition Switch) is located on the Air/Fuel Valve. To check the switch,
proceed as follows:

Purge Switch Open During Purge

1. Set the unit’s ON/OFF switch to the OFF position. Place the unit in manual mode and set

the valve position between 25% and 30%.

2. Remove the Air/Fuel Valve cover by rotating the cover counterclockwise to unlock it (see

Figure 6-7).

3. Remove one of the two wires (#171 or #172) from the Purge Switch (Figure 6-8).

4. Initiate a unit start sequence.

5. The unit should begin its start sequence, then shut down and display PRG SWITCH OPEN

DURING PURGE.

6. Replace the wire on the Purge Switch and depress the CLEAR button. The unit should

restart.

Figure 6-7: Air/Fuel Valve Cover Location

AIR/FUEL VALVE COVER
(ROTATE CCW TO REMOVE)