Benchmark 6000 Boiler Installation, Operation & Maintenance Manual

CHAPTER 3 – OPERATION

OMM-0086_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 45 of 210

GF-133

Ph.: 800-526-0288

03/20/14

Table 3-4: Configuration Menu

Menu Item Display

Available Choices or Limits

Default

Minimum

Maximum

Internal Setpt

Lo Temp Limit

Hi Temp Limit

130°F



Unit Type

KC Boiler, KC Boiler LN,

BMK Blr Std, BMK Blr Std Dual,

BMK Blr LN, BMK Blr LN Dual

KC Water Heater,

KC Water Heater LN,

Innovation WH

BMK Boiler LN

Unit Size
(Only the unit sizes
available for the Unit
Type will be displayed)

750 MBH, 1000 MBH,

1500 MBH, 2000 MBH,
2500 MBH, 3000 MBH,

6000 MBH

6000 MBH

Fuel Type

Natural Gas or Propane

Natural Gas



Boiler Mode

Constant Setpoint,

Remote Setpoint,

Direct Drive,

Combination,

Outdoor Reset

Constant

Setpoint

Remote Signal
(If Mode = Remote
Setpoint, Direct Drive
or Combination)

4 – 20 mA/1 – 5V

0 -20 mA/0 – 5V

PWM Input

(Legacy BMS

), Network

4 – 20 mA,

1-5V

Outdoor Sensor

Enabled or Disabled

Disabled

*Bldg Ref Temp
(If Mode = Outdoor
Reset)

40°F

230°F

70°F

*Reset Ratio
(If Mode = Outdoor
Reset)

0.1

9.9

1.2

*System Start Tmp
(If Outdoor Sensor =
Enabled)

30°F

100°F

60°F

Setpt Lo Limit

40°F

Setpt Hi Limit

60°F

Setpt Hi Limit

Setpt Lo Limit

210°F

140°F

Temp Hi Limit

40°F

210°F

160°F

*NOTE

The Bldg Ref Temp and Reset Ratio Menu Items are only
displayed when the Outdoor Sensor is set to “Enabled”.