Table B-2: Fault Messages

FAULT MESSAGE

FAULT DESCRIPTION

AIRFLOW FAULT

DURING PURGE

The Blower Proof Switch opened during purge,
or air inlet is blocked.

AIRFLOW FAULT

DURING IGN

The Blower Proof Switch opened during ignition.

AIRFLOW FAULT

DURING RUN

The Blower Proof Switch opened during run.

DELAYED

INTERLOCK OPEN

The Delayed Interlock is open.

DIRECT DRIVE

SIGNAL FAULT

The direct drive signal is not present or is out of range.

EXHAUST TEMP

HIGH

The exhaust temperature has exceeded

EXHAUST TEMP

SENSOR OPEN

Exhaust Temperature Sensor is open.

EXHAUST TEMP

SENSOR SHORT

Exhaust temperature sensor is shorted.

FFWD TEMP

SENSOR FAULT

The temperature measured by the Feed Forward (FFWD)
Sensor is out of range.

FLAME LOSS

DURING IGN

The Flame signal was not seen during ignition or lost within 5
seconds after ignition.

FLAME LOSS

DURING RUN

The Flame signal was lost during run.

HEAT DEMAND

FAILURE

The Heat Demand Relays on the Ignition board failed to
activate when commanded.

HIGH EXHAUST
TEMPERATURE

The Exhaust Temperature has exceeded 200°F.

GAS PRESSURE

FAULT

The High Gas Pressure Limit Switch OR Low Gas Pressure
Limit Switch is open

.

HIGH WATER

TEMPERATURE

The temperature measured by the Outlet Sensor exceeded
the Temp Hi Limit setting.

HIGH WATER TEMP

SWITCH OPEN

The High Water Temperature Limit Switch is open.

IGN BOARD

COMM FAULT

A communication fault has occurred between the PMC board
and Ignition board.

IGN SWTCH CLOSED

DURING PURGE

The Ignition Position Limit switch on the Air/Fuel Valve closed
during purge.